Tools & HE accessories Tools & HE accessories

Heat transfer fluid

  • Tyfocor® L
  • Tyfocor® L-eco
  • Tyfocor® LS
  • Tyfocor® GE

Heat transfer fluid Tyfocor® L
Canister of 11 kg concentrate
Article-no: 290 000 10 | Price bracket B 58,10 €   Add to wish list

Heat transfer fluid Tyfocor® L-eco
Canister of 11 kg concentrate
Article-no: 290 000 15 | Price bracket B 63,00 €   Add to wish list

Heat transfer fluid Tyfocor® LS
Canister of 10 l readymix
Article-no: 290 000 20 | Price bracket B 36,50 €   Add to wish list

Heat transfer fluid for heat pump systems Tyfocor® GE
Canister of 11 kg concentrate
Article-no: 290 026 60 | Price bracket B 54,70 €   Add to wish list

Physical and chemical characteristics
Concentrate Tyfocor® L
Form liquid
Colour colourless
Odour nearly odourless
Antifreeze temp. < -50 °C
(40 Vol-%) -23,7 °C
Boiling point >150 °C
Flashing point >100 °C
Density at 20 °C approx. 1.054 ... 1.058 g/cm³
Example mixing ratio Tyfocor®L:
1 tank Tyfocor® L + 15.6 l of water = 26 l of readymix with 40 Vol % (-23.7 °C)

Readymix Tyfocor® LS
Form liquid
Colour red fluorescent
Odour product-specific
Antifreeze temp. -28 °C
(40 Vol-%) not allowed
Boiling point >100 °C
Flashing point none
Density at 20 °C approx. 1.032 ... 1.035 g/cm³
 
Concentrate Tyfocor® GE
Form liquid
Colour bluegreen
Odour product-specific
Antifreeze temp. -18 °C
(bei 40 Vol-%) -24°C
Boiling point >175 °C
Flashing point >100 °C
Density at 20 °C 1.100 ... 1.130 g/cm³
Example mixing ratio Tyfocor®GE:
1 tank Tyfocor® GE + 15.6 l of water = 26 l of readymix with 40 Vol % (-23.7 °C)



Propylene-glycol-water mixtures are commonly used as the heat transfer fluid. An antifreeze concentration of about 40 % of glycol in the mixture prevents the system from damage. even at temperatures of -21 °c, the system remains in an operable state. temperatures below this protection point will cause the formation of ice pulp, which however is not able to destroy tubes and piping. However, today's high-end flat collectors and direct-flow vacuum tube collectors may cause the premature degrading of conventional heat transfer fluid at high stagnation temperatures. In order to prevent this process, the operating pressure of the system can be limited to 4 bar or a high-temperature-resistant heat transfer fl uid can be used.

Important notice about the use of heat transfer fluids:

  • Only use heat transfer fluid which is suitable for the system it is used in
  • All parts of the system that come into contact with fluids must be glycolresistant
  • Concentrations of more than 50 % of glycol are to be avoided in order to achieve optimum efficiency
  • Tyfocor® L/L-eco, LS and GE are not subject to the ordinance of Hazardous Substances.

    Product photos

    Tyfocor (17422 kB)

    Please note that RESOL – Elektronische Regelungen GmbH owns the sole copyright on objects, documents, graphics, pictures, audio and video documents, texts, etc. published and created by RESOL – Elektronische Regelungen GmbH. Copying, distribution to third parties, changing the contents or using these contents in electronic or printed publications is not permitted without the explicit approval of RESOL.

    The cTuVUS certification confirms that the controller meets the demands of the UL 60730-1A and CSA E60730.1 standards.
    The cLCus certification confirms that the controller meets the demands of the UL 60730-2-9 and CSA - E60730-2-9-01 standards.
    The cLCus certification confirms that the controller meets the demands of the UL 60730-1A and CSA E60730.1 standards.