DeltaSol® Fresh 20
Inputs:
3 inputs for Pt1000, 2 digital Grundfos Direct Sensors™ (VFD 2 - 40 Fast)
Outputs:
2 semiconductor relays and 1 PWM output
Switching capacity:
1 (1) A 240V ~ (semiconductor relay)
Total switching capacity:
2 A 240 V~
Power supply:
100 ... 240 V~ (50 ... 60 Hz)
Supply connection:
type Y attachment
Power consumption:
< 1 W (Standby)
Mode of operation:
Typ 1.Y
Rated impulse voltage:
2,5 kV
Data interface:
RESOL VBus®
VBus® current supply:
35 mA
Housing:
plastic, PC-ABS and PMMA
Mounting:
wall mounting, mounting into patch panels is possible
Indication/Display:
System-Monitoring-Display
Operation:
3 push buttons at the front
Ingress protection:
IP 20 / DIN EN 60529
Protection class:
I
Ambient temperature:
0 ... 40 °C
Pollution degree:
2
Dimensions:
172 x 110 x 46 mm
DeltaSol® Fresh 100
Inputs:
10 inputs for Pt1000, 1 V40 impulse inputs, inputs for 1 Grundfos Direct Sensors™ (digital), 1 input for a CS10 irradiation sensor
Outputs:
4 semiconductor relays, 1 potential-free relay, 4 PWM outputs (convertible to 0-10 V signal outputs)
Switching capacity:
1 (1) A 240 V~ (semiconductor relay)
4 (1) A 24 V=/240 V~ (potential-free relay)
Total switching capacity:
4 A 240 V~
Power supply:
100 ... 240 V~ (50 ... 60 Hz)
Supply connection:
type Y attachment
Data interface:
RESOL VBus®, SD card slot
Housing:
plastic, PC-ABS and PMMA
Mounting:
wall mounting, mounting into patch panels is possible
Indication/Display:
full graphic display
Operation:
7 push buttons
Ingress protection:
IP 20 / DIN EN 60529
Protection class:
I
Ambient temperature:
0 ... 40 °C
Pollution degree:
2
Dimensions:
198 x 170 x 43 mm